Nevada Type H Hood and Duct Cleaning Exam Topics: NFPA 96 and NAC 477 Study Guide
What the Nevada State Fire Marshal hood and duct cleaning exam covers: NFPA 96 inspection for grease buildup and cleaning, hoods, ducts and fans, and the NAC 477 rules for Type 1 exhaust systems, labels and reports.
Nevada Type H Hood and Duct Cleaning Exam Topics: NFPA 96 and NAC 477 Study Guide
The Nevada State Fire Marshal publishes no outline for the hood and duct cleaning exam. What it does publish is the rule, and NAC 477.770 says what you must know: NFPA 96, section 11.4 (2017 edition) and "the applicable provisions of this chapter", meaning NAC 477. NAC 477.780 adds that systems with grease are cleaned under that same NFPA 96 section.
The table below is the blueprint our practice exams use. It is ours, not the State Fire Marshal's.
| Area | What it covers | Our weight |
|---|---|---|
| NFPA 96: inspection and cleaning | Chapter 12 (2017: Chapter 11): inspection for grease buildup, cleaning, maintenance | 40% |
| NFPA 96: hoods, ducts and fans | Chapters 4 to 9: clearances, hoods, grease filters, ducts, access panels, fans | 26% |
| NAC 477 | Licensing, the exam, labels, contracts and deficiency reports | 24% |
| NFPA 96: fire protection and special operations | Chapters 10 to 17: extinguishing systems, shutoffs, solid fuel, mobile cooking | 10% |
NFPA 96 inspection and cleaning
The rule names one section, so expect it to be heavily tested. In the 2021 edition it is section 12.4 and the surrounding chapter:
- Table 12.4 inspection frequencies: monthly for solid fuel cooking, quarterly for high-volume cooking (24-hour, charbroiling, wok), semiannually for moderate volume, annually for low volume (churches, day camps, seasonal businesses, senior centers);
- the inspection is done by a properly trained, qualified and certified person acceptable to the authority having jurisdiction;
- a measurement system of deposition triggers cleaning: a grease depth gauge comb, cleaning at 0.078 in. (2000 µm), or 0.125 in. (3175 µm) in a fan housing, down to 0.002 in. (50 µm);
- during cleaning: lock out switches that could be activated accidentally, keep fire suppression components working unless a qualified person services them, no flammable solvents, no chemicals on fusible links, no powder or coating afterward;
- after cleaning: restore access panels and cover plates, put a dated company label near any panel you removed, reposition dampers and diffusers, return switches to operation, leave a certificate on the premises and give the owner a written report of areas that were inaccessible or not cleaned;
- related maintenance: fusible links replaced at least semiannually, grease drip containers emptied at least weekly, cooking equipment serviced at least annually.
Hoods, ducts and fans
You have to reach every part of the system, so know how it is built: clearances to combustibles, listed hoods and grease filters, grease duct construction, access panels (where they go, how big, gaskets and sealants), and exhaust fans and their access.
NAC 477
The state rules are short, and their numbers make easy questions:
- 477.300: who needs a license (cleaning a Type 1 hood and duct is listed work), records kept 10 years, a certificate holder directly supervises uncertified employees;
- 477.770: license vs certificate of registration, the 75% exam score, the employer letter, city or county business licenses, supervision of uncertified helpers;
- 477.780: the cleaning contract and reports stay at the site; deficiencies (excessive grease, inaccessible areas, non-compliant access panels, fans that are not commercial or cleanable, missing filters) go to the authority having jurisdiction by the close of business the next business day; contract expirations are reported the same way;
- 477.790: the stick-on label on the hood: punched for the service and date, signed by the certificate holder (no number or date stamps), printed with the service schedule, last and next service dates, the servicer's name and certificate number, the company and its license number; "impairment" and "deficiency" written across it in bold black letters when they apply, and the owner has 30 days to correct a deficiency;
- 477.773 and 477.775: the owner's periodic inspection of the exhaust and ventilation system and the airflow verification done by a certified technician;
- 477.313 and 477.325: retakes after 15 days, at most three attempts a year, and the fees.
Study plan
- Week 1: NFPA 96 Chapter 12. Learn Table 12.4, the depth-gauge numbers and the cleaning steps in order.
- Week 2: NAC 477.770 to 477.790. Read them twice; they are four pages.
- Week 3: NFPA 96 Chapters 4 to 9, focusing on access panels, clearances and fans.
- Week 4: timed practice at 75% or better.
Our Nevada Type H practice exams follow this blueprint: 50 questions, 75% to pass, each answer citing the NFPA 96 (2021) or NAC 477 section behind it. Start with the free sample test.
Read next: who needs the license and certificate and what happens on exam day.
Sources: NAC 477 (revised 6/26/2026) and NFPA 96 (2021 edition), read November 2026. NAC 477 names NFPA 96 (2017); our questions use the 2021 numbering.