What's on the Detroit Fire Alarm Specialty Technician Exam?
The City of Detroit's Fire Alarm Specialty Technician exam is 36 multiple-choice questions in 1½ hours, open book, and you need 75%. The city's guide says it is based on three books:
- the Skilled Trades Regulation Act, PA 407 of 2016;
- NFPA 72, National Fire Alarm and Signaling Code, 2013 edition (you bring your own);
- NFPA 70, the National Electrical Code, 2017 edition.
There is no Detroit ordinance, local amendment, Part 8 or PA 230 on the list.
Our blueprint
Detroit does not publish how many questions come from each book, so this split is ours. It weights NFPA 72 most heavily because the exam requires you to bring it, and it gives Article 760 the largest NEC share because it is the fire alarm article. Our full-length practice exam draws in these proportions.
| Area | Questions (our blueprint) |
|---|---|
| NFPA 72: fundamentals, definitions and circuits (Ch. 3, 10, 12) | 4 |
| NFPA 72: initiating devices (Ch. 17) | 5 |
| NFPA 72: notification appliances (Ch. 18) | 4 |
| NFPA 72: protected premises, emergency communications and household systems (Ch. 21, 23, 24, 26, 29) | 3 |
| NFPA 72: inspection, testing and maintenance (Ch. 14) | 4 |
| NEC Article 760, fire alarm systems | 6 |
| NEC general rules, grounding, wiring methods and Articles 725, 770 and 800 | 5 |
| Skilled Trades Regulation Act (PA 407) | 5 |
| Total | 36 |
NFPA 72 (2013): where to look
- Chapter 10, Fundamentals: equipment listing, primary and secondary power, secondary power capacity, and the personnel qualifications for installers and service technicians.
- Chapter 12, Circuits and Pathways: pathway class designations and survivability.
- Chapter 17, Initiating Devices: smoke and heat detector spacing and location, duct and air-sampling detection, sprinkler waterflow and supervisory signal devices.
- Chapter 18, Notification Appliances: audible levels above ambient, visible appliance placement and candela, and textual and graphical appliances.
- Chapter 14, Inspection, Testing and Maintenance: who is responsible, what each test involves and how often.
- Chapters 23, 24 and 29: protected premises systems, emergency communications (voice evacuation and mass notification) and household fire alarm systems.
The 2017 NEC
Article 760 carries the most weight: power-limited and non-power-limited fire alarm circuits, separation from other conductors, cable types and substitutions, support, and the branch circuit that supplies the fire alarm control unit. Around it, expect the general rules of Articles 90, 100 and 110, grounding and bonding in Article 250, Article 300 wiring methods, and Articles 725, 770 and 800 for the other low-voltage, optical fiber and communications circuits a fire alarm system shares space with.
PA 407
Expect the definitions (fire alarm system, fire alarm specialty technician), the fire alarm contractor and specialty technician license requirements, the one technician to two apprentices ratio, the rule that a specialty technician license can qualify only one fire alarm contractor license, permits, and penalties.
The edition traps
Most current study material is written for NFPA 72 (2019 or 2022) and the 2023 NEC. Three differences catch candidates:
- Testing frequencies: in NFPA 72 (2013) they sit in Table 14.4.3.2 together with the test methods. From 2016 they have their own table, 14.4.5.
- Article 725: the 2017 NEC keeps Class 1, 2 and 3 circuits in one Article 725. The 2023 NEC splits them across Articles 722, 724 and 725.
- The ampacity table is Table 310.15(B)(16) in the 2017 NEC, not Table 310.16.
Every question in our Detroit practice exam cites the 2013 or 2017 section, so you learn the numbering you will see in the room.
A study plan
- Tab NFPA 72 (2013) at Chapters 10, 14, 17, 18 and 23. You will spend most of your lookups there.
- Read Article 760 end to end in the 2017 NEC, then the Article 725 rules it points to.
- Read PA 407's Article 7 (the electrical article, sections 339.5701 to 339.5739) once, plus the general licensing and penalty sections.
- Sit a timed set. 36 questions in 90 minutes is 2½ minutes each.
Try our free Detroit practice test, or go to the full exam prep. For eligibility, see Detroit Fire Alarm Specialty Technician requirements; for what to bring, see exam day.