What's on the CSA ASCR2 Sprinkler Exam: Books, the 17 Score-Report Topics, and What Gets Missed
The books and editions for CSA's ASCR2 sprinkler exam (NFPA 13 2025 with 2022 accepted, 13D, 13R, 14, 25), the 17 topics on the score report, CSA's most-missed list, the CPVC and data sheet material, and the friction loss and elevation math.
Contents
What's on the CSA ASCR2 Sprinkler Exam
CSA's ASCR2 is 101 questions in 2.5 hours, open book, with an 80% pass mark. CSA's own summary is that it "goes into detailed code criteria dealing with sprinkler spacing, obstructions, hangers, seismic fittings, clearance of piping, ceiling pockets, small room rule, types of systems, air maintenance, drainage, and more," plus basic hydraulics and OSHA. It also says: "This exam covers a lot of material."
CSA publishes no percentages. It does publish the topics your score report breaks out, a list of the items candidates miss most, and a detailed study guide (updated March 4, 2025). This article works from those.
The books, and the editions to bring
| Book | Edition CSA lists | Notes |
|---|---|---|
| NFPA 13 | 2025, with 2022 accepted | Handbook recommended |
| NFPA 13D | 2022 or 2025 | |
| NFPA 13R | 2022 or 2025 | |
| NFPA 14 | 2024 | |
| NFPA 25 | 2023 | Handbook recommended |
| CSA Supplemental Sprinkler Exam Material | March 2025 | CPVC manual, data sheets, OSHA material |
| CSA sprinkler study guide | March 4, 2025 | |
| OSHA 3120, Control of Hazardous Energy | CSA download | May be brought in if bound |
These editions apply to exams requested on or after April 1, 2025.
Using NFPA 13 (2022)? CSA accepts it. In its words, there may be "one or two questions on the exam that changed in the 2025 edition such as with elevator pit protection," and you should answer those the way the study guide presents them. The guide's main example is that the 2025 edition no longer requires sprinklers in elevator pits. The guide also lists 2025 changes that the 2025 exams would not test, such as vacuum dry and preaction systems, supplemental sprinklers under obstructions, and K-factor rules for ceilings over 30 feet. Check the current guide for its latest list.
NFPA 13 was reorganized in 2019 and items moved again between 2022 and 2025, so a reference you remember from an older book is probably somewhere else now. Questions that cite a section usually give both editions' numbers where they differ, and a question on a new rule often starts "Effective with the 2025 edition ...".
A note on our practice questions. Our ASCR2 practice exam is written on NFPA 13 (2022), NFPA 13D and 13R (2022) and NFPA 25 (2023), which are all editions CSA accepts. NFPA 14 is the exception: we write on the 2019 edition, and CSA tests 2024, so check our standpipe answers against your own copy. Our practice does not cover CSA's CPVC manual or the manufacturer data sheets. We write no questions on them; study those from CSA's free download. CPVC and Manufacturer Listings are 2 of the 17 topics on CSA's score report. CSA does not publish how many questions each topic gets, so the share is not known, but expect a real block of the exam that our practice exams do not include.
The 17 score-report topics
A failed score report gives a score for each topic. CSA says a topic can have as few as 2 questions or as many as 20, but it doesn't say which. The topics are:
- NFPA 13 General
- NFPA 13 Spacing
- NFPA 13 Systems
- NFPA 13 Sprinklers
- NFPA 13 Hangers
- NFPA 13 Definitions
- NFPA 13 Seismic
- Calculations
- NFPA 25 General
- NFPA 14 Definition
- NFPA 14 General
- CPVC
- NFPA 13D General
- NFPA 13R General
- NFPA 13R Sprinkler
- OSHA
- Manufacturer Listings (Datasheets)
Seven of the 17 are NFPA 13, which matches the study guide's emphasis.
What CSA says gets missed most
- seismic fittings and pipe penetrations;
- sprinkler temperature ratings near sources of heat;
- obstructions to discharge, such as columns, signs and exam-room curtains;
- spacing, area of coverage, and distance between sprinklers and from walls;
- the small room rule and compartments;
- CPVC cure times for new installations versus cut-ins;
- CPVC in basements and exposed installations;
- CPVC hanger spacing and bracing;
- NFPA 25 impairments;
- NFPA 14 standpipe classes; and
- calculations of friction loss and elevation pressure.
NFPA 13: where the study guide spends its time
The guide's 66 numbered items lean heavily on NFPA 13. The themes that recur:
- Spacing and coverage: area per sprinkler, spacing along and between branch lines, distance from walls, sloped ceilings, ceiling pockets, and the small room rule. The guide lists the definitions and sections for the small room rule in both editions.
- Obstructions: the "three times rule", soffits, suspended signs, walls that stop short of the ceiling, privacy curtains, and obstructed versus unobstructed construction.
- Systems: wet, dry, preaction and deluge, single and double interlock, air supply and nitrogen, trip pressure, time-to-water limits, and drains.
- Hangers and seismic: hanger types and rod sizes, post-installed anchors in concrete, flexible hose support, sway bracing, flexible couplings and clearance around penetrations.
- Components and special cases: dry-barrel sprinklers, response types and RTI, temperature ratings, upright frame orientation, bathroom omissions, elevators and stairs, storage concepts, ESFR obstruction rules and high-volume low-speed fans.
- Underground and acceptance: depth of cover, flushing rates, and backflow forward-flow testing.
The guide's best single piece of advice: always read past the section you land on. An exception a few paragraphs later often changes the answer.
NFPA 13D, 13R, 14 and 25
- 13D and 13R: how their scope and trade-offs differ from NFPA 13, including spacing, temperature ratings near heat, fire department connections, flow alarms and garages. The guide points to specific chapters in each, and notes a 2025 change requiring drains on 13R risers 2.5 inches or larger.
- NFPA 14: Class I, II and III standpipes, automatic versus manual, wet versus dry, and valve locations.
- NFPA 25: impairments, valves, dry and preaction valves, fire pump run times, damaged sprinklers and internal inspections. Installers do renovations and repairs, and every new system must come with a copy of NFPA 25 for the owner.
CPVC and data sheets: CSA's supplemental material
CSA's Supplemental Sprinkler Exam Material is a 117-page booklet you print, bind and bring in. It contains:
- Viking and Reliable sprinkler data sheets, for questions marked [Sprinkler Data] or [Manufacturer Listings];
- a Reliable dry-pipe valve data sheet and FlexHead flexible hose data;
- the Spears CPVC installation manual; and
- OSHA material on elevator pits, confined spaces and lockout/tagout.
The data sheet questions test whether you can read a listing: deflector distance, minimum pressure by room size, extended coverage spacing, and how many bends a flexible hose may have. These can differ from NFPA 13's general rules, so be careful whether a question asks what NFPA 13 allows or what the data sheet requires. For CPVC, know cure times (new versus cut-in), deflection, hangers, the flange bolt tightening sequence, and diagrams where you take half of a table dimension.
The math
CSA's calculations are short, and each one turns on a single idea. With our own numbers:
- Friction loss: loss per foot times length. At 0.08 psi per foot over 45 feet, the loss is 3.6 psi.
- Equivalent length: a fitting or flexible drop is given as equivalent feet of pipe. A drop rated at 40 equivalent feet, in pipe losing 0.15 psi per foot, loses 40 × 0.15 = 6.0 psi.
- Elevation: 0.433 psi per foot. A 120-foot column of water exerts 120 × 0.433 = 52.0 psi at the bottom.
- Minimum pipe size: if the street gives 65 psi and the riser needs 52 psi, you can lose up to 13 psi. Pick the smallest pipe whose total friction loss stays under that.
Practice that matches the exam
Our Colorado sprinkler fitter practice exams include a timed ASCR2 exam with 101 questions, 2.5 hours and the 80% pass mark, written on NFPA 13, 13D, 13R, 14 and 25, with a code reference on every answer. They do not cover CSA's CPVC manual or the manufacturer data sheets (2 of the 17 score-report topics), so study those from CSA's free download. Try the free sample test, or read who accepts ASCR2.
Sources: CSA's Sprinklers, Test Info and Frequent Questions pages, its sprinkler study guide (updated March 4, 2025) and its Supplemental Sprinkler Exam Material (March 4, 2025), read November 2026. The calculation examples use our own numbers to show CSA's methods. CSA does not publish topic weights. The emphasis here is our reading of the study guide, not CSA's.
Ready to pass Colorado State Sprinkler Fitter Registration?
Start your prep with unlimited practice tests and codebook-referenced answers.