What's on the Colorado State Sprinkler Fitter Exam: Books, Editions, and Topics
The DFPC State Fitter Exam covers NFPA 13, 13D, 13R, 14, 20, 22, 24 and 25 and the Colorado fire suppression rules. The editions to bring, the topics that matter most, and the Colorado rules fitters get tested on.
Contents
What's on the Colorado State Sprinkler Fitter Exam
The Colorado Division of Fire Prevention and Control (DFPC) writes its own State Fitter Exam for sprinkler fitter registration. It is 85 questions in 2.5 hours, you need 60 right (70%), and it is open book: you bring your own code books, and DFPC hands you a copy of the Colorado rules at the exam.
DFPC publishes the list of books but no topic outline and no breakdown of how many questions come from each one. So the useful question is what each book is likely to be asked for, and how to find it fast.
The books, and the editions to bring
The exam tests the codes DFPC has adopted, so the edition matters. Bring these:
| Book | Edition | What it covers |
|---|---|---|
| NFPA 13 | 2019 | Installation of sprinkler systems |
| NFPA 13D | 2019 | One- and two-family dwellings and manufactured homes |
| NFPA 13R | 2019 | Low-rise residential occupancies |
| NFPA 14 | 2019 | Standpipe and hose systems |
| NFPA 20 | 2019 | Stationary fire pumps |
| NFPA 22 | 2018 | Water tanks for private fire protection |
| NFPA 24 | 2019 | Private fire service mains |
| NFPA 25 | 2020 | Inspection, testing and maintenance of water-based systems |
| 8 CCR 1507-11 | Current rule | Colorado's fire suppression program (provided at the exam) |
Colorado amends one standard. In NFPA 25 (2020), DFPC replaces section 5.3.4.4 on antifreeze systems with its own text. Listed antifreeze solutions are required. Systems installed before September 30, 2012 may keep factory-premixed propylene glycol up to 30% or glycerine up to 38% by volume, or up to 40% and 50% with an approved risk assessment.
Newer editions of these books are numbered differently in places, especially NFPA 13, which was reorganized in 2019. Answers are graded to the editions above, so bring those editions, not the newest ones.
NFPA 13: the heart of the exam
NFPA 13 is the installation standard a fitter works from every day, and it is where we put the largest share of our practice questions. The parts worth tabbing:
- Sprinkler location and spacing: maximum and minimum distances, coverage areas, distance below the ceiling and deflector position, and obstructions to discharge.
- System types: wet, dry, preaction and deluge, and when each is required or allowed.
- Hanging, bracing and restraint: hanger spacing by pipe size, seismic bracing and restraint, and clearance where pipe passes through walls and floors.
- Components and materials: listed pipe and fittings, valves, fire department connections, drains and test connections.
- Acceptance testing: hydrostatic test pressure and duration, dry pipe trip tests and flushing.
NFPA 25: inspection, testing and maintenance
Colorado's rule puts inspection, testing and maintenance inside the sprinkler trade, and many fitters do ITM work. Expect frequency questions (weekly, monthly, quarterly, annual, five-year), impairment handling, obstruction investigation, and the gauge, valve and alarm tests.
The other standards
- NFPA 14: standpipe classes, hose connection locations, minimum flow and pressure, and the acceptance tests.
- NFPA 24: underground mains, depth of cover, thrust restraint, flushing rates and hydrostatic testing.
- NFPA 20: pump installation, the acceptance test, churn and rated flow, and drivers and controllers.
- NFPA 22: tank types, tank heating and the tank's own inspection requirements.
- NFPA 13D and 13R: where residential sprinklers are required, where they may be omitted, and the residential design and installation rules. We hold the 2022 editions of these two books, one cycle newer than the 2019 editions DFPC tests, so check those practice answers against your own copy.
The Colorado rules: easy points if you know where to look
DFPC hands out 8 CCR 1507-11 at the exam, so you don't have to memorize it. You do need to know what is in it. The parts a fitter gets asked about:
- Who must register (Section 5): the definition of a Sprinkler Fitter and its exclusions, working only for a registered contractor, the 8,000-hour or apprenticeship route, and the manufacturer certificate for CPVC or PEX.
- Registration and renewal: the July 1 to June 30 year, the renewal and grace windows, and 2.4 CEUs a year under Table 5.4.2, with work hours capped at 1.6.
- On the job (Section 8): carry your registration and show it to an inspector who asks, do the work in a workmanlike manner, follow the AHJ's fire watch requirements before leaving a system out of service, and supervise no more than three apprentices while staying on site.
- Plans and calculations (Section 6): flow tests must be less than a year old, and water supply data for new systems is reduced by 10%, up to 10 psi, except for NFPA 13D systems.
- Installation: approved plans kept on site, piping left accessible for inspection, and hydrostatic, operational and flush tests witnessed and signed by a certified Fire Inspector.
- System tags: a white INSTALL tag for new work and major alterations, which stays for the life of the system; green OPERATIONAL after an annual inspection with no problems; yellow DEFICIENCY; red IMPAIRMENT; and blue REPAIR, attached to the yellow or red tag once the problem is fixed.
- Impairments and complaints: an impairment found during work must be reported to the fire department and the AHJ within 24 hours, and fitters must report significant or repeated violations to DFPC.
- Enforcement (Section 10): warnings, letters of admonition, suspension, revocation and fines.
How to use an open-book exam
At 85 questions in 150 minutes you have under two minutes each. That is enough time to look up a rule you know how to find, but not enough to search the book from the front for every question. Tab the books, and answer what you know before you look anything up. The exam-day guide has more on pacing.
Our Colorado sprinkler fitter practice exam mirrors the real one: 85 questions, 2.5 hours, 70% to pass, written against the editions DFPC tests, with the code reference on every answer. Try the free sample test first, or read about registration requirements.
Sources: DFPC's State Fitter Exam page, read November 2026; 8 CCR 1507-11 as amended in 2022; and 8 CCR 1507-101 §3.2.4 (adopted standards and the NFPA 25 antifreeze amendment) as amended effective December 30, 2025. DFPC does not publish a topic outline. The emphasis here is our reading of the reference list, not DFPC's.