What's on the California Fire Extinguisher Exam? Title 19, Not NFPA 10
OSFM publishes no outline, question count or pass mark for its Type 1 fire extinguisher exam (OSFMFEI02). Why California tests Title 19 Chapter 3 rather than NFPA 10, the intervals, tags and distances to know, and a closed-book study plan.
Contents
What's on the California Fire Extinguisher Exam? Title 19, Not NFPA 10
What OSFM publishes about the content
Very little. For the Type 1 Certificate of Registration exam (Pearson VUE OSFMFEI02, "Fire Extinguisher 1"), the Office of the State Fire Marshal publishes:
- no content outline or topic weights;
- no question count;
- no time limit;
- no passing score.
What is published: the exam is computer-based, multiple choice and closed book, delivered by Pearson VUE. Anyone quoting an official question count or a percentage per topic is guessing.
The regulations themselves are the best guide. A Type 1 certificate covers the recharge and maintenance of any or all types of portable extinguishers (19 CCR 595.9), and California spells out how that work is done in its own rules.
California tests Title 19, not NFPA 10
This is the most important thing to know if you trained in another state. Most states enforce NFPA 10. California does not, at least not directly. Section 906.2 of the 2025 California Fire Code, in force since January 1, 2026, requires portable extinguishers to be "selected, installed and maintained in accordance with this section and California Code of Regulations, Title 19, Division 1, Chapter 3."
That chapter, Title 19 Chapter 3, is California's own extinguisher rulebook. It covers much of the same ground as NFPA 10, but with its own section numbers, its own tag and label rules, and some of its own requirements. Study Title 19. Use NFPA 10 only as background.
How our practice exam is weighted
Because OSFM publishes no outline, we built our own blueprint from what Title 19 Chapter 3 and the licensing law require a Type 1 technician to know. These weights are ours, not OSFM's:
| Area | Our weight |
|---|---|
| Inspection, maintenance and recharging | 35% |
| Selection and installation | 20% |
| Tags, collars, labels and seals | 20% |
| Licensing law (Health and Safety Code and Title 19) | 15% |
| Hydrostatic testing | 10% |
The sections below follow the same order.
Inspection, maintenance and recharging
This is the core of a service technician's work and of our practice exam. Know these intervals without looking them up:
- Monthly inspection (574.1).
- Annual maintenance by a licensed concern (575.1).
- Early service. Maintenance may not be done more than 30 days early without the owner's written agreement (575.1(h)).
- Non-rechargeable extinguishers come out of service at 12 years (575.1(b)).
- Six-year maintenance of stored-pressure dry chemical and halogenated agent extinguishers that need a 12-year hydrostatic test (575.4, 575.6).
- CO2 extinguishers get internal maintenance at the 5-year hydrostatic test (575.5).
- AFFF and FFFP agent is replaced every 3 years (575.8).
For recharging, know the pressurizing gas rules:
- Nitrogen used to pressurize extinguishers must have a dew point of -60°F or lower (578.6).
- The regulator must be set no more than 25 psi above the extinguisher's service pressure (578.5).
And know when an extinguisher leaves service for good. A condemned extinguisher gets a red tag (577.1), and Title 19 lists the obsolete types that may no longer be kept in service (577.2).
Selection and installation
Title 19 Chapter 3 includes its own classification, selection and distribution rules. Tables 2 and 3 set the maximum travel distances. The headline numbers:
| Hazard | Maximum travel distance |
|---|---|
| Class A | 75 ft |
| Class B | 30 or 50 ft, depending on the extinguisher's rating |
| Class K | 30 ft |
| Class D | 75 ft |
Mounting heights are classic exam material:
- Extinguishers of 40 lb or less: top no more than 5 ft above the floor.
- Heavier extinguishers: top no more than 3 1/2 ft above the floor.
- In all cases, the bottom at least 4 in. off the floor.
Also know the fire classes (A, B, C, D and K) and which agents suit each.
Tags, collars, labels and seals
This is where California differs most from NFPA 10, and where an out-of-state technician is most likely to lose points. Article 9 (596 to 596.5) prescribes:
- The annual maintenance tag: 4 3/4 in. by 2 3/8 in., worded "Do Not Remove by Order of the State Fire Marshal," carrying the E and EE numbers, and signed by the technician. No rubber stamps for the signature.
- The Verification of Service collar, placed on the extinguisher after internal maintenance or recharge. Collars are not used on cartridge-operated or CO2 extinguishers.
- Hydrostatic test labels, with their own required content.
- Color: none of these service tags, collars or labels may be red. Red is reserved for condemned extinguishers.
The statute backs this up: H&SC 13183 requires everyone who services an extinguisher to attach a tag with the date and their signature.
Licensing law
Expect questions on the rules that govern the technician, not just the extinguisher. The requirements guide walks through them; the numbers to know are:
- Types 1, 2 and 3 certificates (595.9), and the separate concern licenses, Types A to F and L (595.5);
- minimum age 18 (595.3);
- the 90-day supervised window for new employees (H&SC 13175.1);
- 15 days before a retake, 90 days to test once eligible, a 72-hour window to challenge a question, and possible re-examination every four years (595.10);
- certificates expire December 31, with renewal due by November 1 (H&SC 13179, 13180);
- carry your certificate on the job (595.11).
Hydrostatic testing
Hydrostatic testing has its own certificates (Types 2 and 3), but Type 1 technicians need to know when a cylinder is due. Title 19 Table 5 sets the intervals, which fall into two groups: 5 years (CO2, water, AFFF/FFFP, wet chemical and stainless steel dry chemical extinguishers) and 12 years (halogenated agents, and dry chemical or dry powder in mild steel, brazed brass or aluminum shells). Know which extinguisher falls in which group, and how the hydro schedule ties to the 6-year maintenance and the CO2 internal maintenance above.
A closed-book study plan
- Read Title 19 Chapter 3 end to end. It is the exam's real subject, and it is free. OSFM publishes it with the Health and Safety Code sections in its Fire Extinguisher Law & Regulations booklet.
- Make an interval sheet. Monthly, annual, 3-year, 5-year, 6-year and 12-year, with the extinguisher types each applies to. Drill it until you can write it from memory.
- Learn the numbers in the tables. Travel distances, mounting heights, tag dimensions, nitrogen dew point and regulator setting.
- Learn the tag rules as rules. What goes on the tag, when a collar is used and when it isn't, and why nothing may be red.
- Unlearn NFPA 10 where it differs. If you trained elsewhere, note every place Title 19 uses its own procedure or label.
- Practice without the book. You cannot bring anything into the exam room.
Practice
Our California fire extinguisher practice exam is written to Title 19 Chapter 3 and the licensing law, with a section citation on every answer. Because OSFM publishes no format, we use neutral settings of our own: 50 questions in 90 minutes, with a 70% practice pass mark, weighted by the blueprint above. Start with the free 10-question sample test.
For what to expect at Pearson VUE, see California fire extinguisher exam day. Licensed in Maryland or another NFPA 10 state? Compare what Maryland's NFPA 10 exam covers.
Content comes from 19 CCR Chapter 3 and the California Health and Safety Code, as compiled in the OSFM Fire Extinguisher Law & Regulations, January 2022 Edition, and from section 906.2 of the 2025 California Fire Code. Exam format comes from the Pearson VUE OSFM candidate handbook. OSFM publishes no outline for this exam; check with the OSFM fire extinguisher program for updates before your exam date.