Sizing Secondary Power for Fire Alarm Systems
1 contact hours · earn 1 NICET CPD point
Size the secondary (battery) supply the way NFPA 72 expects — standby and alarm loads, duty periods, and derating — and bank a CPD point toward your recert.
What you’ll learn
- Explain why NFPA 72 requires both a primary and a secondary power supply for a fire alarm system
- State the standby and alarm durations required for protected-premises systems and how they differ for emergency voice/alarm communication and mass-notification systems
- Distinguish standby (quiescent) current from alarm current and identify where each value comes from on the manufacturer battery-calculation worksheet
- Perform a complete secondary-power battery calculation, including the 25% aging factor, and select a standard battery size
- Apply battery-selection constraints — charger capacity, the 48-hour recharge rule, and temperature derating — and recognize the field errors that fail acceptance testing
Who it’s for: NICET Fire Alarm Systems certholders keeping their credential current, and designers who spec secondary power supplies.
Preview
1. Why a fire alarm system needs two power supplies
A fire alarm system earns its place in a building on a single promise: that it will detect a developing fire and warn occupants in time to escape, whether or not anything else in the building is still working. The event most likely to knock out a fire alarm system is the very event it exists to survive. A fire compromises wiring, trips breakers, and prompts responders or building staff to kill utility power to the structure. A system that depends on a single source of energy is a system that fails at the worst possible moment. For that reason, the National Fire Alarm and Signaling Code (NFPA 72) has, for its entire modern history, required that every fire alarm system be served by two independent power supplies: a primary supply and a secondary (standby) supply.
The primary power supply is the source the system runs on every ordinary day. In the overwhelming majority of installations it is a dedicated branch circuit fed from the building light-and-power service, terminating at a locked or otherwise secured overcurrent device that is marked in red and identified as serving the fire alarm system. The primary supply carries the full working load of the panel and everything connected to it, and — critically — it is the source that keeps the secondary battery charged. When the primary supply is healthy, the battery does essentially nothing except float on the charger, waiting.
The secondary power supply is the reserve. Its job is to carry the entire system through a loss of primary power for a defined period, and then still have enough energy left to drive every notification appliance in the building through an actual alarm. In most protected-premises systems the secondary supply is a sealed lead-acid (SLA) storage battery, sometimes called a valve-regulated lead-acid (VRLA) battery, sized specifically for that duty and housed inside or immediately adjacent to the control unit. NFPA 72 permits other forms of secondary supply — most notably an engine-driven generator paired with a shorter-duration battery, and, in some editions and for some system types, a listed uninterruptible power supply — but the storage battery is by far the most common arrangement and is the focus of this course.
The distinction that a technician must internalize is that the secondary supply is not a convenience feature or a "nice to have." It is a code-mandated capacity that is calculated, not estimated, and is verified during acceptance testing. An undersized battery is a defect that will fail an acceptance test, and — far more importantly — is a defect that can leave a building silent during a real fire once the utility power is gone. The purpose of this course is to make the calculation second nature, to explain where each number in it comes from, and to surface the handful of mistakes that most often produce an undersized or non-compliant secondary supply.
Everything that follows rests on one mental model. Picture the battery as a fuel tank measured in amp-hours. Two demands draw fuel from that tank after utility power is lost: a long, quiet demand while the system simply supervises the building — the standby load — and a short, heavy demand when the system actually goes into alarm and drives its horns and strobes — the alarm load. The battery must hold enough fuel for the full standby period plus the full alarm period, with a margin added for the fact that batteries lose capacity as they age. Size the tank for the worst realistic day, add the margin, and round up to a real battery you can actually buy. That is the entire discipline, and the rest of this course is simply the detail behind it.
Finish the course and earn your CPD certificate.
FAQ
Does this course count toward my NICET recertification?
Yes. You earn 1 NICET CPD point per contact hour toward the recertification of your NICET Fire Alarm Systems certification. Points are awarded on your certificate of completion after you finish the course and pass the end quiz.
How long does it take?
About one hour of focused content plus a short end quiz — one contact hour, one CPD point.
How do I get my certificate?
Finish the course content and pass the end quiz; your dated certificate of completion (with CPD points) is generated instantly for download.